What is the CFI2 fault on an Altivar (ATV600, ATV900 and ATV340) drive?
Issue:
Customer has the CFI2 fault on an Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980, and APM)
Altivar Machine Drive (ATV340)
Environment:
All serial numbers
Cause:
N/A
Resolution:
The CFI2 is Configuration Transfer Error Fault.
Occurs when a configuration file can not be loaded to the device, or the configuration is not compatible with the drive.
Possible Causes:
Customer has the CFI2 fault on an Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980, and APM)
Altivar Machine Drive (ATV340)
Environment:
All serial numbers
Cause:
N/A
Resolution:
The CFI2 is Configuration Transfer Error Fault.
Occurs when a configuration file can not be loaded to the device, or the configuration is not compatible with the drive.
Possible Causes:
- The was an unsuccessful or interrupted configuration file transfer.
- The stored configuration (HMI) was loaded from an different firmware. For example a file saved on a newer version drive can not be loaded into an older firmware version.
- Check firmware
- Firmware should be compatible on both drives
- Load a compatible configuration.
- Use SoMove to transfer configuration from another drive, or modify the saved SoMove configuration to match the drive being programmed.
- Perform a factory setting
- [Main Menu] [File Transfer] [Factory Settings]
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.