Issue
Opening a Unity 11 application in Unity 11.1 returns the message 'No valid PLC Project found.
Product Line
Unity
Environment
Windows 10
Resolution
If you try to open a Unity 11 application in Unity 11.1 and it contains an EIO configuration, the error messages
'No Valid PLC Project found' and 'Process failed. 1 errors(s), 0 Warning(s)." could get returned. This will occur
if the bus number 1 exist in the EIO configuration.
The issue has been corrected in Unity 12 and will no longer occur.
To resolve the issue, it is recommended to update to Unity 12. In the event that you cannot update to Unity 12,
the following workaround canbe used:
Opening a Unity 11 application in Unity 11.1 returns the message 'No valid PLC Project found.
Product Line
Unity
Environment
Windows 10
Resolution
If you try to open a Unity 11 application in Unity 11.1 and it contains an EIO configuration, the error messages
'No Valid PLC Project found' and 'Process failed. 1 errors(s), 0 Warning(s)." could get returned. This will occur
if the bus number 1 exist in the EIO configuration.
The issue has been corrected in Unity 12 and will no longer occur.
To resolve the issue, it is recommended to update to Unity 12. In the event that you cannot update to Unity 12,
the following workaround canbe used:
- Open the application with Unity 11.
- Change the EIO bus number from 1 to a different number other than 1.
- Save the application as a '.sta' or '.zef' file'
- Open the application with Unity 11.1.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.