Issue:
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.