Hôm nay chúng tôi có thể giúp gì cho bạn?

PME@local host is not detected when Detect Event Sources is selected in the ENM Configuration after ENM 8.3.x is installed.

Issue:
PME@local host is not detected when Detect Event Sources is selected in the ENM Configuration
after ENM 8.3.x is installed, it should be showing as the screen shot below
Event Sources


Product Line:
Event Notification Module (ENM) 8.3
Power Monitoring Expert (PME) 8.x

Environment:
Windows Server

Cause:
Unable to configure ENM since is not detecting PME@localhost.

Resolution:
Need to make sure ENM is licensed before trying to configure ENM.
Verify that ENM is activated and listed under Floating License Manager.

Please Note:

Approved in PME 2020+, ENM is integrated directly into the PME web app under Settings → Alarms → Notifications.




Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings