Issue
This Resolution describes why there is a minimum firmware version of 2.18 for a BMXCRA31210 at a PV07.
Some Ethernet ports of a BMXCRA31210, at a PV07 or higher, will not function if the firmware is downgraded to any version less than 2.18
Product Line
BMXCRA31210 PV07
Resolution
This Resolution describes why there is a minimum firmware version of 2.18 for a BMXCRA31210 at a PV07.
Some Ethernet ports of a BMXCRA31210, at a PV07 or higher, will not function if the firmware is downgraded to any version less than 2.18
Product Line
BMXCRA31210 PV07
Resolution
- Firmware version 2.18 was created to operate with the new PV07 module and is compatible with previous PV versions.
- Firmware version 2.18 has the exact same functionality as version 2.16. There are no fixes and no improvements. The requirement for firmware version 2.18 was due to a component change in PV07 and higher modules.
- BMXCRA31210 modules at PV07 are not compatible with firmware versions less than 2.18.