Connecting an EGX150 to a serial RS485
Issue
The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.
Product Line
Link150, EGX150
Environment
EGX150 serial connections
Cause
The EGX150 does not use the standard RS-485 connector.
Resolution
Table 1: Connector RJ 45 Pinout
| Pin Number | Color | Signal name | Description |
| 1 | Orange/White striped | Rx- | Receive Data - |
| 2 | Orange | Rx+ | Receive Data + |
| 3 | NC | No Connection | |
| 4 | Blue | Tx+ | Transmit Data + |
| 5 | Blue/white striped | Tx- | Transmit Data - |
| 6 | - | NC | No Connection |
| 7 | - | NC | No connection |
| 8 | - | GND | Ground |
Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
Cut the other end (that is to be connected to your slave device) to expose the wires.
A1. 2-Wire RS-485 connection
Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)
A2. RS-485 2-Wire with Link150 Cable Adapter Connection Diagram
B1. 4-Wire RS-485 connection
Table 2: RJ45 Master/Slave Pinout
| RJ45 Pin Number | Master | Slave |
| 1 | Rx- | Tx- |
| 2 | Rx+ | Tx+ |
| 4 | Tx+ | Rx+ |
| 5 | Tx- | Rx- |
B2. RS-485 4-Wire with Link150 Cable Adapter Connection Diagram
Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.