Issue:
Using a braking resistor with Altivar Process ATV930 variable seed drive.
Product Line:
Altivar Process ATV930 variable speed drive
Environment:
Where a braking resistor is needed
Cause:
Documentation
Resolution:
Use PA+ and PB power terminals of an Altivar900 series drives to connect a braking resistor
References with a "C" letter at the end: the drive does not have an internal braking transistor (chopper). Additional braking unit is required to connect a braking resistor
Using a braking resistor with Altivar Process ATV930 variable seed drive.
Product Line:
Altivar Process ATV930 variable speed drive
Environment:
Where a braking resistor is needed
Cause:
Documentation
Resolution:
Use PA+ and PB power terminals of an Altivar900 series drives to connect a braking resistor
References with a "C" letter at the end: the drive does not have an internal braking transistor (chopper). Additional braking unit is required to connect a braking resistor