Issue:
End user reads a modbus register and is getting a value other than what is expected
Product:
PowerLogic and ION meters
Environment:
Modbus Registers
Cause:
The Power meters, based on the manufacturing location, may have an offset.
In some meters the registers start from Zero and others may start from 1. So, the published register list varies accordingly.
Example: If Register 2017 is for Frequency of the meters it will read 60HZ.
But for the meter with offset the Register 2016 will read 60HZ.
Resolution:
Check the Modbus Register List for the specific meter you are trying to read for any indication that the registers have an offset. If it does you will need to shift the register by that offset to read the correct register.
End user reads a modbus register and is getting a value other than what is expected
Product:
PowerLogic and ION meters
Environment:
Modbus Registers
Cause:
The Power meters, based on the manufacturing location, may have an offset.
In some meters the registers start from Zero and others may start from 1. So, the published register list varies accordingly.
Example: If Register 2017 is for Frequency of the meters it will read 60HZ.
But for the meter with offset the Register 2016 will read 60HZ.
Resolution:
Check the Modbus Register List for the specific meter you are trying to read for any indication that the registers have an offset. If it does you will need to shift the register by that offset to read the correct register.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.