What are the main differences between feeder and motor mode with Easergy P3?

Issue:
Need to understand the main differences between feeder mode and motor mode in Easergy/Powerlogic P3.

Product Line:
- Easergy/ Powerlogic P3
- Applies to Easergy/Powerlogic P3 relays that support feeder and motor application modes

Environment:
- Easergy/Powerlogic P3 relay configuration
- Application mode selection
- Protection function configuration

Cause:
Feeder mode and motor mode use different scaling references and enable different protection functions based on the selected application.

Resolution:
  • In feeder mode, current scaling is based on the CT nominal.
  • In motor mode, current scaling is based on the motor nominal current (Imot).
  • Some protection functions appear or disappear depending on the selected mode.
  • In feeder mode, feeder-related functions such as auto recloser are available.
  • In motor mode, motor-related functions such as motor start-up supervision and other motor protection functions are available.
  • Common protection functions, such as overcurrent protection, may be available in both modes, but their settings and scaling are interpreted according to the selected application mode.
  • If the expected function is not visible, verify that the relay is configured for the correct application mode.


Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings