Issue:
Trying to set an ATV320 with terminals as run command and 0-10VDC reference from AI1.
Product Line:
Altivar 320
Environment:
All
Cause:
Programing
Resolution:
Wiring:
DI1 and +24V as 2 wire control run command.
0-10VDC can be wired into AI1 and COM.
If using a potentiometer then wiring would look like +10, AI1, and COM.
Drive is already programmed to do this function from the factory.
Under CONF, FULL, I/O, TCC will need to be set to 2C.
Under CONF, FULL, CTL, FR1 will need to be set to AI1
Trying to set an ATV320 with terminals as run command and 0-10VDC reference from AI1.
Product Line:
Altivar 320
Environment:
All
Cause:
Programing
Resolution:
Wiring:
DI1 and +24V as 2 wire control run command.
0-10VDC can be wired into AI1 and COM.
If using a potentiometer then wiring would look like +10, AI1, and COM.
Drive is already programmed to do this function from the factory.
Under CONF, FULL, I/O, TCC will need to be set to 2C.
Under CONF, FULL, CTL, FR1 will need to be set to AI1