Issue
Network discovery returns the error 'Chassis ID conflict.
Product Line
Connexium Network Manager
Environment
Windows 10
Resolution
After discovering the network, Connexium Network manager returns the error 'Chassis ID conflict'

The error message indicates that both devices (i.e., 192.168.11.3 and 192.168.11.4) have the same LLDP chassis ID.
The reason for the error is because LLDP (Link Layer Discovery Protocol) requires the chassis ID to be unique. The chassis ID is based on the system name.
To resolve the error, check the system name for both devices and verify that they are unique using the following steps.
If the 'system Name' is not unique, use the following steps to change it.

Network discovery returns the error 'Chassis ID conflict.
Product Line
Connexium Network Manager
Environment
Windows 10
Resolution
After discovering the network, Connexium Network manager returns the error 'Chassis ID conflict'
The error message indicates that both devices (i.e., 192.168.11.3 and 192.168.11.4) have the same LLDP chassis ID.
The reason for the error is because LLDP (Link Layer Discovery Protocol) requires the chassis ID to be unique. The chassis ID is based on the system name.
To resolve the error, check the system name for both devices and verify that they are unique using the following steps.
- Open the 'device' list by clicking on the 'Device' tab.
- Verify that the names are unique.
If the 'system Name' is not unique, use the following steps to change it.
- Open the network topology map by clicking on the 'Map'.
- Right click on the device icon.
- Select 'Properties'.
- Chnge the name.
- Click on OK.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.