Issue:
What causes an SoF [Overspeed Fault] on an ATV630, ATV930 or ATV340?
Product Line:
ATV630, ATV660, ATV680
ATV930, ATV960, ATV980
ATV340
Environment:
All serial numbers
Cause:
SOF during acceleration.
Resolution:
This fault can be caused by incorrect motor nameplate information in the drive, incorrect motor control settings for the application, or problems with the encoder feedback signal (ATV930/ATV340).
To resolve, go to the Main menu and Simply Start menu to ensure the motor nameplate information is correctly entered:
Nominal Motor power (nPr)
Nom Motor Voltage (unS)
Nom Motor Current (nCr)
Nominal motor Freq (FrS)
Nominal motor Speed (nSP)
If problem remains, goto Complete Settings (menu 5) / Motor parameters / Motor data and change Motor Param Choice to Mot Cosinus. Then enter the Power Factor of the Motor in parameter Motor 1 Cosinus Phi.
Also under Motor Parameters try changing to a different Motor Control Type. Selection may depend on the drive and the application, but common settings are U/V VC Standard or U/F VC 5pts.
If an Encoder is used, review the encoder wiring, programming and mechanical connection to the motor. Instability or driving load too high.
If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command
Remedy
Verify the motor parameter settings.
Verify the size of the motor/drive/load.
Verify and close the contacts between the motor and the drive before applying a Run command.
Clearing the Error Code
This detected error requires a power reset.
What causes an SoF [Overspeed Fault] on an ATV630, ATV930 or ATV340?
Product Line:
ATV630, ATV660, ATV680
ATV930, ATV960, ATV980
ATV340
Environment:
All serial numbers
Cause:
SOF during acceleration.
Resolution:
This fault can be caused by incorrect motor nameplate information in the drive, incorrect motor control settings for the application, or problems with the encoder feedback signal (ATV930/ATV340).
To resolve, go to the Main menu and Simply Start menu to ensure the motor nameplate information is correctly entered:
Nominal Motor power (nPr)
Nom Motor Voltage (unS)
Nom Motor Current (nCr)
Nominal motor Freq (FrS)
Nominal motor Speed (nSP)
If problem remains, goto Complete Settings (menu 5) / Motor parameters / Motor data and change Motor Param Choice to Mot Cosinus. Then enter the Power Factor of the Motor in parameter Motor 1 Cosinus Phi.
Also under Motor Parameters try changing to a different Motor Control Type. Selection may depend on the drive and the application, but common settings are U/V VC Standard or U/F VC 5pts.
If an Encoder is used, review the encoder wiring, programming and mechanical connection to the motor. Instability or driving load too high.
If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command
Remedy
Verify the motor parameter settings.
Verify the size of the motor/drive/load.
Verify and close the contacts between the motor and the drive before applying a Run command.
Clearing the Error Code
This detected error requires a power reset.
Đã phát hành cho: Schneider Electric Việt Nam










Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.