Here are 4 combinations of ATV configuration that show the difference between SLFV and FS2V
1. Pump curves entered and activated flow estimation used and FS2A (pump flow sensor assignment) is not configured ==> SLFV is caclutated from pump curves. FS2V is copy of SLFV.
2. (Pump curves not activated or flow estimation not used) and FS2A is not configured ==> SLFV=0, FS2V=0
3. (Pump curves not activated or flow estimation not used) and FS2A=AIx analog input ==> SLFV=0, FS2V=value from the sensor on AIx
4. Pump curves entered and activated flow estimation used and FS2A=AIx ==> SLFV is caclutated from pump curves. FS2V=value from sensor on AIx
To sum up, If there is a pump flow sensor (F2SA is configured) then FS2V provides information from the flow sensor. If there is no pump flow sensor, FS2V takes the value from SLFV.
1. Pump curves entered and activated flow estimation used and FS2A (pump flow sensor assignment) is not configured ==> SLFV is caclutated from pump curves. FS2V is copy of SLFV.
2. (Pump curves not activated or flow estimation not used) and FS2A is not configured ==> SLFV=0, FS2V=0
3. (Pump curves not activated or flow estimation not used) and FS2A=AIx analog input ==> SLFV=0, FS2V=value from the sensor on AIx
4. Pump curves entered and activated flow estimation used and FS2A=AIx ==> SLFV is caclutated from pump curves. FS2V=value from sensor on AIx
To sum up, If there is a pump flow sensor (F2SA is configured) then FS2V provides information from the flow sensor. If there is no pump flow sensor, FS2V takes the value from SLFV.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.