What are the recommendations for connecting PTC to the Altistart ATS48?
What are the recommendations for connecting PTC to the Altistart ATS48?
Product Line:
ATS48
Environment:
All
Cause:
Wiring
Resolution:
Manual shows the following;
PTC1, PTC2 - Total resistance of probe circuit: 750 Ω at 25 °C/77 °F
• For example, three 250 Ω probes in series
PTC monitoring also needs to be enabled in the programming:
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.