Issue:
ATV320 with EtherNet/IP is not starting with assemblies 20/70.
Product Line:
ATV320
Environment:
Ethernet IP
Cause:
n/a
Resolution:
With assemblies 20/70, it's mandatory to respect dedicated drive configuration on : CD1, FR1, CHCF, CD2, FR2, CCS, RFC parameter
But in addition, it's mandatory to write via acyclic messaging the NetRef and NetCtrl parameters.
With Assemblies 20-70 «NetRef» and «NetCtrl» objects must be set by explicit messaging to control the drive by Network.
NetCtrl and NetRef are CIP object.
NetCtrl
This object defines if requests Run/Stop control come from local or from the network.
NetRef
This object defines if Requests torque or speed reference to be local or from the network.
Here with assemblies 20-70 its necessary there is no bit inside the assembly object so it’s necessary to send these 2 CIP objects by acyclic exchange
To activate the command by EtherNet/IP you need to write 1 in NetCtrl.
To activate the reference by EtherNet/IP you need to write 1 in NetRef.
You need to write these 2 CIP objects after:
- drive power on
- Disconnection of DeviceNet/Ethernet cable.
Note: The default setting (value 0) of NetCtrl and NetRef will applied each time you Power ON the drive or after DeviceNet/Ethernet cable disconnection.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.