Hôm nay chúng tôi có thể giúp gì cho bạn?
BMX AHI /AHO analog module s: What exactly means refresh and response time?
In Documentation we talked about refresh time, response time for the BMX AHI module .
Difficulty is to undesrtand what is the meanning and difference about those two terms .
Response time only makes sense when talking about a specific channel.
Response time is the delay time between external stimulation and the PLC read value, it only makes sense when talking about a channel. Because the different channels get the different external stimulations.
If all the eight channels for AHI change from 4mA to 20mA at the same time (change finished within 0ms), then the read values for all the eight channels will arrive 10000 after 50ms (assume 4-20mA = 0-10000).
Difficulty is to undesrtand what is the meanning and difference about those two terms .
Response time only makes sense when talking about a specific channel.
Response time is the delay time between external stimulation and the PLC read value, it only makes sense when talking about a channel. Because the different channels get the different external stimulations.
If all the eight channels for AHI change from 4mA to 20mA at the same time (change finished within 0ms), then the read values for all the eight channels will arrive 10000 after 50ms (assume 4-20mA = 0-10000).
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.