SEPAM Trip Curves: Type 1 versus Type 1.2
Issue
User would like to understand the difference in tripping characteristics between Type 1 and Type 1.2 trip curves on SEPAM relays.
Product
SEPAM Series 20
SEPAM Series 40
SEPAM Series 80
Environment
SFT2841 configuration software
Cause
Confusion arises due to the availability of two curve types (Type 1 and Type 1.2) that appear similar but have different pickup conditions, which affects protection coordination and relay response.
Resolution
SEPAM relays offer two selectable trip curve types: Type 1 and Type 1.2.
- Type 1 Curve:
- Pickup occurs when the measured current equals the relay threshold setting
- Condition: I = Is
- Type 1.2 Curve:
- Pickup occurs when the measured current reaches 1.2 times the relay threshold setting
- Condition: I = 1.2 × Is
- After pickup, it follows the same tripping characteristics as the standard Type 1 (IEC) curve
Key difference:
- The only distinction between the two curves is the pickup level
- Once pickup is reached, both curves behave identically in terms of time-current characteristics
For further analysis and visualization:
- Refer to the available trip curve calculators for SEPAM and MiCOM relays
- Review the comparison charts showing Type 1 vs Type 1.2 characteristics
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.