Issue:
On an ATV630, the drive ramps all the way to low speed and high speed when my +/- speeds are pulsed.
Product Line:
Altivar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Drive ramps all the way up and down without stopping in between
Resolution:
This could be caused by any of the following:
On an ATV630, the drive ramps all the way to low speed and high speed when my +/- speeds are pulsed.
Product Line:
Altivar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Drive ramps all the way up and down without stopping in between
Resolution:
This could be caused by any of the following:
- The pulse isn't actually a pulse. Instead you're providing a sustained signal to the digital input
- Acceleration time is too short. +/- speed ramping is based on acceleration speed
- The pulse doesn't drop out long enough for the drive to recognize that it has dropped. Repeated input activation at too high speed can cause this
- Make sure you're actually pulsing the inputs for activation
- Try pulsing the inputs with a jumper wire from +24V to see if the behavior changes
- Adjust acceleration time longer
- Adjust deactivation of the digital inputs to a longer amount of time so the drive realizes the input has deactivated. The drive needs to see the signal drop in order to stop ramping
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.