Issue
User would like to know the differences between the Digital Output Behaviour Modes "Normal", "Timed", and "Trip Coil"
Product Line
PM5300
PM5500
Environment
Front panel or ION Setup
Resolution
Descriptions of the three (3) digital output behaviour modes are below.
Normal:
User would like to know the differences between the Digital Output Behaviour Modes "Normal", "Timed", and "Trip Coil"
Product Line
PM5300
PM5500
Environment
Front panel or ION Setup
Resolution
Descriptions of the three (3) digital output behaviour modes are below.
Normal:
- Digital output will turn ON when the specified external or alarm condition is met as defined in Control Mode
- The digital output remains ON only while the alarm is active
- Digital output will turn ON when the specified external, demand sync, alarm, or energy condition is met as defined in Control Mode
- The digital output remains ON for the time period (in seconds) defined in the "On Time" setup parameter
- Digital output will turn ON when the specified external or alarm condition is met as defined in Control Mode
- The digital output remains ON until the command number 6004 is sent to the meter from a PLC or PC.
- Please check the command structure in the Modbus register list at PowerLogic PM5000 Series (PM5100, PM5300, PM5500) Modbus Register List
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.