Issue
Customer send multiple commands from SCADA within short interval of time ( in ms ). What settings shall be configured in NOR module to accept this commands successfully.
Product Line
BMXNOR0200 V1.7 IR19, WinPP104 ( Licensed Version with customer )
Environment
Windows 10 64 Bit Build 10.1703.1, Control Expert V14.0
Resolution
In the webpage of NOR when configured as server, access the parameter "CMD Queue Size" by Channel > server > session > paramter > Advanced Properties > CMD Queue Size
This CMD Queue size allows us to configure the NOR to accept multiple commands for various datatypes C_SC, C_SO etc in parallel. By default it is zero. User needs to configure
this value to like 10 to perform some test.
Customer send multiple commands from SCADA within short interval of time ( in ms ). What settings shall be configured in NOR module to accept this commands successfully.
Product Line
BMXNOR0200 V1.7 IR19, WinPP104 ( Licensed Version with customer )
Environment
Windows 10 64 Bit Build 10.1703.1, Control Expert V14.0
Resolution
In the webpage of NOR when configured as server, access the parameter "CMD Queue Size" by Channel > server > session > paramter > Advanced Properties > CMD Queue Size
This CMD Queue size allows us to configure the NOR to accept multiple commands for various datatypes C_SC, C_SO etc in parallel. By default it is zero. User needs to configure
this value to like 10 to perform some test.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.