PME Web Alarms show "Unable to update the result. The server either timed out or returned invalid result."
Issue
PME Web Applications Alarms tab does not show Alarms and a red error message appears stating: 'Unable to update the result. The server either timed out or returned invalid result. If this problem persists please contact the system administrator.'
In the PME ApplicationModules log, the following errors are shown:
- Failed to load the resx file 'EnumAndEvent' for the culture 'en', --- >
System.IO.FileNotFoundException: Could not find file 'C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\EnumAndEvent.en.resx'. - Failed to load the resx file 'IONNames' for the culture 'en', --- >
System.IO.FileNotFoundException: Could not find file 'C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\IONNames.en.resx'.
Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Web Applications
Cause
The language associated with EnumAndEvent.en.resx and IonNames.en.resx are not reading correctly.
Resolution
1. On the PME server, navigate to …\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc
2. Make a copy of the EnumAndEvent.en.resx and IONNames.en.resx files
3. Rename the copies to EnumAndEvent.en-US.resx and IONNames.en-US.resx
4. Open the Windows Start menu and search for "Command Prompt"
5. Right-click on Command Prompt > Run as Administrator
6. Type the following command then press Enter to run:
- iisreset
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.