If you have checked the basic commissioning steps (Smartlink powered on, pairing, communication periods, channel attribution) you can refer below.
This issue can occur for SmartLink SI D / SI B with old firmware revision when they are used in environment with high density wireless traffic (intensive RF environment). In this case, you need to replace your SmartLink SIB / SI D by a PowerTagLink A9XMWD20 or A9XMWD100.
Switch OFF / ON the wireless devices to commute the wireless device in "waiting for pairing" status and launch the wireless discovery on the gateway to pair them.
If you have not the possibility to switch OFF / ON you wireless devices (case of powertag associated to critical load) please contact your Schneider Electric technical support.
This issue can occur for SmartLink SI D / SI B with old firmware revision when they are used in environment with high density wireless traffic (intensive RF environment). In this case, you need to replace your SmartLink SIB / SI D by a PowerTagLink A9XMWD20 or A9XMWD100.
Switch OFF / ON the wireless devices to commute the wireless device in "waiting for pairing" status and launch the wireless discovery on the gateway to pair them.
If you have not the possibility to switch OFF / ON you wireless devices (case of powertag associated to critical load) please contact your Schneider Electric technical support.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.