How to configure a serial daisy chain to have devices split between multiple I/O Servers in Power SCADA Operation (PSO) 9.0

Issue
Some of the devices on a serial daisy chain need to live on a different I/O Server than the rest of the devices on that daisy chain.

Product Line
Power SCADA Operation 9.0

Environment
Studio, Topology, PSO server

Cause
In PSO, a specific Port cannot be used on more than one I/O Server.

Resolution
To split a daisy chain between multiple I/O Servers, a unique Port is needed for each I/O Server. For example, assume a daisy chain of 10 devices needs 5 serial devices on I/O Server 1, and the other 5 on I/O Server 2. The port for the 5 serial devices on I/O Server 1 is named North_IO1_devices. A second unique port needs to be defined for the devices that will exist on I/O Server 2, perhaps named South_IO2_devices.
  1. This port can be created for I/O Server 2 in the Ports table located in Topology > Components and Mapping. The IP address will be the same for both ports since it is the same gateway device/daisy chain.
  2. Once the Port is created, Navigate to Topology > IO Devices. Assign the newly created port to the desired devices for I/O Server 2, and change the I/O Server fetid for each device to the appropriate name.
  3. Save and compile the project.
*Note: If there were parameters in the Citect.ini defined for the original port, those parameters will have to be added for the additional port that was created, as well.*

Schneider Electric Việt Nam

Tìm hiểu thêm

Tìm hiểu thêm

Bạn cần trợ giúp?

Công cụ chọn sản phẩm

Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.

Nhận báo giá

Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.

Nơi mua hàng?

Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.

Trung tâm Hỗ trợ

Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.