How is calculated the processor load value in the BMXNOC0401 communication module?
Issue:
How is calculated the Processor load value in the BMXNOC0401 communication module?

Product Line:
M340
BMXNOC0401

Environment:
Web page

Resolution:
Processor load value is a ratio between “CPU non-Idle tasks Time” and “Total CPU time”( if idle is 30% then CPU utilization is 100-30=70%).
The CPU is a multi-task system, the execution order of the different type of tasks depend on their priorities .
In the case of the BMXNOC0401, the following tasks have an impact on its load :
  • Server and client traffic packets per second as each packet is inspected and a transaction occurs
  • Size of I/O scanner image: bigger the scanner load, the longer it takes to copy from the xbus
  • PLC CPU scan time, as we have to transfer the I/O scanner twice a scan cycle.
  • General network traffic like multicast and broadcast traffic as it must be inspected

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings