Issue
Translator failure for PM5300 series device type in the system log, causing issues in real-time and data log.
- Transaction error. Device: 'Source Name'. Client: 'IONSERVICES.SRVMTTO'. Reason: 'Translator failure'
- Could not find a configurable label value for configLabel=8 configLabelHandle=166723847 IONHandle=254145026
_____________________________________________________________
Product Line
Power Monitoring Expert 2021
Power Monitoring Expert 2020
Power Monitoring Expert 9.0
_____________________________________________________________
Environment
Device Driver
_____________________________________________________________
Root Cause
The PM5300.xml driver located in PME/System/Translator folder is missing the ConfigLabel Ordinal="8" for the ConfigLabelHandle="166723847":
<ModbusInfo IONHandle="254145026" Name="Demand Current Avg - Present" ModbusAddress="403878" RequestType="R" Format="F32-4321" ConfigLabelHandle="166723847" NotAvailableValue="0xFFC00000">
<ConfigLabels Ordinal="0" Value="Demand Current Avg - Present - Thermal"/>
<ConfigLabels Ordinal="1" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="2" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="3" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="4" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="5" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="6" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="7" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="9" Value="Demand Current Avg - Present - Sliding"/>
_____________________________________________________________
Solution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop). *
For the default driver, back up the PM5300.xml file located at $\Power Monitoring Expert\system\translator and follow the steps below:
- Find the exact line: <ModbusInfo IONHandle="254145026" Name="Demand Current Avg - Present" ModbusAddress="403878" RequestType="R" Format="F32-4321" ConfigLabelHandle="166723847" NotAvailableValue="0xFFC00000" in the PM5300.xml file
- Add <ConfigLabels Ordinal="8" Value="Demand Current Avg - Present - Sliding"/> between line ConfigLabel Ordinal 7 and 9 and save the file.
<ConfigLabels Ordinal="7" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="8" Value="Demand Current Avg - Present - Sliding"/>
<ConfigLabels Ordinal="9" Value="Demand Current Avg - Present - Sliding"/>
If the driver had been customized, back up and repeat the steps for the PM5300.xml file located at $\Power Monitoring Expert\config\translators.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.