What could cause the Somove software to no longer communicate over the USB/Serial connection?

Issue:

SoMove will not even launch the serial configuration popup window and is triggering an Root Element error.

Product Line:

Somove Software with the TCSM Serial cable.

Environment:

All

Cause:

The first signs for the problem manifested as a "Root Element" error in Somove.

Check your program manager to see if EAE or EcoStruxure Automation Expert v21.x has been recently installed

Resolution:

The Modbus serial DTM suite and the TCSM cable drivers files may need to be purged or reinstalled.

Contact the Drives Product Support Group for assistance. 888-778-2733 option 2 and option 4.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings