This problem is a known issue and fixed in firmware revisions :
The issue occurs when all conditions below are met :
=> These four conditions may cause byte swapped data (for little endian conversion) on some modbus commands on the I/O scanning devices.
A global power cycle on the rack or hot swap of BMENOC03x1 makes the issue disappear.
We recommend to upgrade the BMENOC03x1 firmware to the latest available version.
- SV1.05 for BMENOC0321
- SV2.16 for BMENOC0301 and BMENOC0311
- SV2.16 for BMENOC0301 and BMENOC0311
The issue occurs when all conditions below are met :
- when using firmware revisions lower than the ones described above
- when re-configuring and re-downloading application with a Modbus IO Scanner configuration into a BMENOC3xx (without doing a power cycle after the download)
- IO Scanner configuration contained a mix of "Read ONLY", "Write ONLY" and "Read/Write" modbus request
- some IO Scanner lines have been deleted and/or added
- when re-configuring and re-downloading application with a Modbus IO Scanner configuration into a BMENOC3xx (without doing a power cycle after the download)
- IO Scanner configuration contained a mix of "Read ONLY", "Write ONLY" and "Read/Write" modbus request
- some IO Scanner lines have been deleted and/or added
=> These four conditions may cause byte swapped data (for little endian conversion) on some modbus commands on the I/O scanning devices.
A global power cycle on the rack or hot swap of BMENOC03x1 makes the issue disappear.
We recommend to upgrade the BMENOC03x1 firmware to the latest available version.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.