Issue
Control Expert stalls at 75% for several minutes after clicking Build Changes or Rebuild All Project.
Product line
EcoStruxure Control Expert (ECE)
Environment
Windows 10, Windows Server 2019
Resolution
This delay is due to 'Rack Viewer variable names'. When this option is selected the Rack Viewer Control Expert checks for each I/O object configured inside the application and if it is linked to a variable name.
In order to decrease the building time, we recommend unselecting this option in Control Expert.
Control Expert stalls at 75% for several minutes after clicking Build Changes or Rebuild All Project.
Product line
EcoStruxure Control Expert (ECE)
Environment
Windows 10, Windows Server 2019
Resolution
This delay is due to 'Rack Viewer variable names'. When this option is selected the Rack Viewer Control Expert checks for each I/O object configured inside the application and if it is linked to a variable name.
In order to decrease the building time, we recommend unselecting this option in Control Expert.
- Click Tools -> Project Settings...
- Click PLC diagnostics -> unselect Rack Viewer variable names
- Click Build -> Rebuild All Project