PowerTag Link SIB password cannot be changed from the admin drop down option in Webpage
Issue
Acti 9 PowerTag Link SIB password cannot be changed from the admin drop down option in Webpage Admin menu.
SIBPW1
SIBPW2

Product Line
Acti9 PowerTag Link SIB

Environment
Acti9 PowerTag Link SIB
FW V2.4.6

Cause
Password change management is not managed from the top admin banner of the webpage. But it is managed in settings menu.

Resolution

Please follow the below is the procedure for changing password. These steps are updated in the user guide of the gateway.
SIBPW3

Note

Since this product is discontinued and there is no more enhancement/engineering/development. Please consider EcoStruxure Panel Server (PAS) as replacement of the gateway.