EcoStruxure Process Expert for Aveva System Platform [2023]- How to troubleshoot license issue of remote Engineering Client

This knowledge base explains the user about the license issue of the remote engineering client.

When the user tries to launch engineering client from remote machine, he faces the error as shown below:
Image-1


Its understood that, though the license is installed locally on the remote client machine, it tries to consume the client license from the system server machine. If the user closes the engineering client on system server machine ,then the remote engineering client gets opened without any issue.

To overcome the above issue, on the license manager of system server machine(ex:127.0.0.1), remote engineering client IP address(ex: 192.168.10.128) has to be configured  along with the system server machine IP address

Keep the default server selection as 127.0.0.1, as shown below.



After doing the above change, flexnet licensing service needs to be restarted on system server machine.

This is applicable for all Ecostruxure Process Expert versions.




Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings