Troubleshooting Geo SCADA Log Files Not Generated - Possible Reasons and Solution.

This article will cover the reasons why log files may not be generating in Geo SCADA and provide solutions to resolve these issues.

  • Permissions Issues
    The Local System account may not have the necessary permissions to write log files. Ensure that the user has the appropriate permissions to write to the log file directory.
  • Configuration Errors
    The logging configuration might be incorrect or disabled in the application settings. Verify the logging configuration settings. Check the registry setting for the log location: HKEY_CURRENT_USER\SOFTWARE\Schneider Electric\ClearSCADA\ViewX\LogFileBase
  • Disk Space
    Insufficient disk space can prevent log files from being created. Check the available disk space and free up space if necessary.

Solution
Deleting the folder and contents at C:/ProgramData/Schneider Electric/ClearSCADA/Logs and then launching ViewX (for ViewX logs) or restarting the server (for Database or driver logs) will recreate the folder with the correct permissions for the Windows user.

Schneider Electric Việt Nam

Tìm hiểu thêm
Sản phẩm:
Tìm hiểu thêm
Sản phẩm:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings