How to maintain L9_SUB behavior after Control Expert is upgraded from 14.1 to 15.3

L9_SUB function block behavior was changed in v15.0 to be consistent with the description in the online help, but inconsistent with how the function block previously behaved in CE14.1. Customer running CE14.1 with no issue but encountered problem when migrated to CE V15.3.

The proposed workaround solution is to first rename the LL984 folder where CE V15.x is installed (for example add “backup” at the end of the folder name). Then copy and paste the attached LL984 folder to the folder where CE V15.x is installed. Refer to attached documents for more details.

Please note that this is not common practice and the behavior of L9_SUB function block(V14.1) is inconsistent with that in the online help.

Schneider Electric Việt Nam

Phần đính kèm
V141_Unity984.zip [129.22 KB]
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:

Bạn cần trợ giúp?

  • Công cụ chọn sản phẩm

    Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.

  • Nhận báo giá

    Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.

  • Nơi mua hàng?

    Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.

  • Trung tâm Hỗ trợ

    Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.

  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings