Hôm nay chúng tôi có thể giúp gì cho bạn?
Report - Multi Device Usage Report - An error occurred while making initial report viewer settings
Issue:
When Generating the Multi-Device Usage Report for a 1-year period in PME 2023, the following error message appears "An error occurred while making initial report viewer settings"
Product Line:
PME 2023
Cause:
A timeout error occurs a few minutes after initiating the report generation.
please refer the attached image for reference.
Resolution:
Database Warning: “This article contains information about editing the database. Please note, editing or updating anything in DB may cause permanent damage and result in PME to function improperly. This procedure should only be performed by users familiar with SQL Server Management Studio. Kindly take a backup of the database before performing any such action."
To resolve the issue, perform the following steps:
- Update Report Timeout to 600 seconds in the Management Console.
- Open SQL Server Management Studio(SSMS), navigate to the ION_Network database, and locate dbo.vCFG_ConfigItems table. Modify the following settings:
- BatchReportRenderTimeout = 3600 seconds
- MaxNumberofRecords = 1200000
- WebService Proxy Timeout = 930 seconds
- Perform the following steps:
- Run iisreset in command prompt with administrator mode
- Restart IONAppMod Services
- Clear browser cache
Please refer to the attached image for configuration details and reference.
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.