No Valid Server License, HTTP 500.19 Error - Duplicate Request Filtering
Issue
Trying to open Web Applications generates an HTTP 500.19 error. Opening thick apps (Designer, Vista) generates a no valid server license error. Cannot add duplicate collection entry of type "add" with unique key attribute "verb" set to "HEAD".
Product Line
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Internet Information Services (IIS)
Power Monitoring Expert Web.Config Files
Cause
There are web.config files for each site PME uses for its Web Applications. Each of these sites has a section dedicated to request filtering for the HTTP methods (verbs) allowed by the web.config. If these settings are reproduced elsewhere, for example in the web.config file in the root of the web directory or in the applicationhost.config files. It is not recommended to change these files directly so, it is best to deal with the request filtering inside the PME web.config files instead.
You can verify that this error is relevant by navigating to localhost\webservices, https:\\[fully qualified domain name]\Webservices or https:\\[IP address]\Webservices.
Resolution
In the following locations, backup each web.config file to a safe location in case revision is required. If PME is not installed on the C drive, navigate to the location where PME is installed.
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\Dashboards
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\EWS
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\WebReach
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\ReportDataService
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\ModelingConfig
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Web
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\Slideshow
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\SystemDataService
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\ApplicationFramework
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\WebServices
Delete everything between <verbs allowUnlisted ="false"> and </verbs>.
It is paramount that these changes are made to ALL of the web.config files listed. Leaving one will generate the same error.
After the lines have been deleted from the web.config files, open CMD prompt as an administrator and run the iisreset command. Open services and restart the IION Application Modules Core Services Host.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.