Implementing a Heartbeat Signal to Trigger Syslog Messages on SAGE RTU
Issue:
Customer needs a method to generate a periodic syslog message to meet NERC CIP compliance by proving syslog functionality for monitoring systems like SPLUNK.
Product:
SAGE RTU (all models supporting syslog and command logging)
Environment:
- Centralized syslog monitoring system (e.g., SPLUNK)
- Requirement for periodic heartbeat messages to validate syslog operation
- RTU configured with syslog enabled
Cause:
There is no built-in “heartbeat” feature in the SAGE RTU to automatically send syslog messages. However, syslog messages can be triggered by logging events such as command executions.
Resolution:
- Recommended Approach:
- Configure an hourly toggling of a Digital Output (DO) point using a Data Transfer point created specifically for this purpose.
- Each toggle will generate an entry in the Command Log, which in turn sends a syslog message to the monitoring system.
- This achieves the heartbeat function without requiring custom code.
- Steps:
- Please refer to the PDF document attached to this article, titled:
“Create an hourly heartbeat DO command that will trigger Command Log to deliver the event notification to Syslog server.”
- Please refer to the PDF document attached to this article, titled:
This method provides an “elegant” solution using existing RTU functionality and satisfies compliance requirements.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.