EAE - TM262L01MDESE8T - Configuration Assistance w/ EAE v25.0
Issue:
Need to program a M262 dPAC using Automation Expert. Unable to deploy the project in a way that allows access to the inputs and outputs integrated into the main module along with the CPU. Not able to configure the hardware properly.
Product Line:
M262 dPAC controller M262L01MDESE8T.
Resolution:
On a M262 dPAC controller the integrated I/O are disabled and not used, and there is currently no plan to enable them.
This is why these I/O cannot be configured in EcoStruxure Automation Expert.
Into the online help, under the Devices User Guides, the M262 Distributed PAC - User Guide shows in the Presentation of the controller that the I/O terminal connector is not used.
Link to online help:
https://product-help.se.com/EcoStruxure Automation Expert/25.0?lang=en-US&theme=Help