SAGE Offline Configuration Tool — “Directory name invalid” on launch
Issue
After launching the SAGE Offline Editor and selecting a configuration, the tool returns “Directory name invalid”, even though the configuration file is in the same directory as the Editor executable. This occurs across multiple Windows versions and compatibility modes.
Product
SAGE RTU
SAGE Offline Configurator Tool (SOCT)
Environment
Windows workstations (various versions); configurations stored on local drives, network shares, or synced folders (e.g., OneDrive/SharePoint/Dropbox).
Cause
These errors are commonly triggered by folder access and path resolution issues—especially when the SOCT or configuration set is located on network-mapped drives, UNC paths, or cloud‑synced folders (e.g., OneDrive). In those scenarios, the tool may not have full access to enumerate the directory, or the path reported to the application is virtualized/sandboxed, causing a “Directory name invalid” response.
Resolution
Follow these steps in order:
- Check the Run-App Directory
Ensure both the SOCT and the configuration folder are on a local path (e.g., C:\Sage\OfflineEditor\ and C:\Sage\Configs\). - Avoid UNC paths (e.g., \\server\share\...) and cloud‑sync locations (OneDrive/SharePoint/Dropbox).
- If needed, copy your configuration set from the network/synced folder to a local C:\ location and retry.
- Run as Administrator
Right‑click the SAGE Offline Configurator Tool executable and select Run as administrator. - This often resolves permission/virtualization issues affecting directory discovery.
- Check Folder Permissions
Verify the configuration directory grants your Windows user Read/Write permissions. - Right‑click folder → Properties → Security → confirm you have Modify/Write.
- Remove Read‑only attributes on the folder and contained files if set.
- Use the Latest Version
Install and use the latest available version, currently V2.1.1.7 (at Nov 25) - If you’re upgrading, unblock the installer (Right‑click → Properties → Unblock), install to a local path, and relaunch as admin.
If the issue persists:
- Shorten overly long paths or remove special characters from folder names.
- Avoid spaces/unicode in top-level directory names as a diagnostic step.
- Test with a new, empty local folder (e.g., C:\Sage\TestConfig\) and a known‑good sample configuration.
- Check that antivirus/EDR isn’t sandboxing the executable; add a temporary allow‑list entry for the Editor and the config folder.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.