How the BMENOP0300 NTP time synchronization works ?

Issue:

How the BMENOP0300 NTP time synchronization works ?

Product Line:

M580 CPUs, BMENOP0300

Environment:

EcoStruxure Control Expert, Windows 10

Resolution:

The BMENOP0300 IEC61850 communication module does not have an internal clock. It requires synchronization with an external time source, which can be either:

  • An NTP server, or
  • The CPU time.

Time synchronization process:

  1. At PLC startup:
    The BMENOP0300 retrieves the time from the CPU and uses it as its local time. This occurs only once during power-up.

  2. If an NTP server is configured in the BMENOP0300 settings:
    The module automatically switches to the NTP server for time synchronization.

  3. If no NTP server is configured:
    The BMENOP0300 continues to use the CPU time obtained at startup.

Important:
To ensure correct time usage for services such as syslog and generated reports, the following settings must match in both the IEC61850 Configuration Tool and the EcoStruxure Control Expert project:

  • Daylight Saving Time (DST) option
  • Time zone configuration
DST and timezone options

Schneider Electric Việt Nam

Tìm hiểu thêm
Sản phẩm:
Tìm hiểu thêm
Sản phẩm:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings