Why BMENUA0100 Syslog Service is not starting using BMENUA0100 version 3.01 and CAE
BMENUA0100 does not support (yet) secured Syslog.
CAE allows us to activate the "Enable security" (and this option is activated by default !!)
When the NUA receives a cyber security configuration from CAE with “secured syslog" enabled, the service is not started on BMENUA0100.
Therefore, before sending a Cyber Security configuration with CAE, please verify that this feature “enabled security” is disabled.
The Secure Syslog feature will not be available in firmware version 3.01. Its development is scheduled for the next release of the BMENUA0100 firmware.
Product Line
BMENUA0100 version 3.01
EcoStruxure Control Expert 16.4
Cybersecurity Admin Expert version 4.2.1