Hôm nay chúng tôi có thể giúp gì cho bạn?

EROE Displays Version Mismatch Warning Following SCADAPack Firmware Upgrade

After upgrading the SCADAPack Edge firmware, users may see a warning indicating a version mismatch between EROE and IoTView:
warning
The warning occurs because the SCADAPack Edge firmware includes a newer version of IoTView than the version reported by EROE.
ComponentVersion
IoTView (included in Edge firmware)23.1.001
EROE23.1.000
When EROE compares its version with the IoTView version reported by the upgraded firmware, it detects that the versions do not match exactly and generates a warning.
Note that the warning is cosmetic and is not typically associated with any loss of functionality.
At this time, the only way to eliminate the warning is to downgrade the SCADAPack Edge firmware to R3.5.3 or R3.4.2, which use a compatible IoTView version. If the newer Edge firmware is required, the warning can be acknowledged and does not, by itself, indicate a communication or functionality issue.