Jak vám dnes můžeme pomoci?

What are the minimum power requirements to power an EGX?

Issue
What does the EGX gateway require for minimum power?

Product Line
EGX100
EGX200
EGX300
EGX400
EGX150

Environment
Control power

Resolution
A 24VDC, 8 Watt (minimum) power supply (plus or minus 10% regulation) is required to power EGX devices.

Additionally, the EGX100, EGX300, and EGX150 do support Power-over-Ethernet (PoE).
However, as per FA209559, do not connect both PoE and external 24VDC power supply or it may result in intermittent communication.

Note: If polarity is reversed on the 24VDC power supply (+/-), the device will not be damaged.  It will continue to function normally once the power supply is returned to the instructed configuration.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie