What type of 10Base-FL Fiber is Required for devices with fiber optic communications?
Issue
What is the best type of 10Base-FL Fiber for 10Base-FL communications
Product Line
ION Devices
Environment
Fiber Optic Communications
Cause
Some devices such as older (pre 2008) models of the ION7650 have a fiber-optic communication hardware ordering option
Resolution
These are the best specifications for the the fiber to be on the 10Base-FL port
* Multi-Mode fiber
* Wavelength: 850 nm
* Connector Type: ST
* Cladding: 62.5/125 um
* Max Length: 2000m
Note: For 100Base-FX communications see What type of 100Base-FX Fiber is Required for devices with fiber optic communications?
What is the best type of 10Base-FL Fiber for 10Base-FL communications
Product Line
ION Devices
Environment
Fiber Optic Communications
Cause
Some devices such as older (pre 2008) models of the ION7650 have a fiber-optic communication hardware ordering option
Resolution
These are the best specifications for the the fiber to be on the 10Base-FL port
* Multi-Mode fiber
* Wavelength: 850 nm
* Connector Type: ST
* Cladding: 62.5/125 um
* Max Length: 2000m
Note: For 100Base-FX communications see What type of 100Base-FX Fiber is Required for devices with fiber optic communications?
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.