Cannot see any PLC data in the PLC Program Viewer of an NOE77111
Issue
Cannot see any PLC data in the 'PLC Program Viewer' web page of a '140NOE77111' Factorycast module.
Product Line
140NOE77111 All versions.
Environment
Web Designer
Resolution
The PLC data in the 'PLC Program Viewer' web page does not get displayed on an '140NOE77111' Factorycast module that does not have a 'WebDesigner' application.
The reason that is does not get displayed is because the 'PLC Program Viewer' option in Unity is only applicable to the 'BMXNOE0110' (Exec firmware version 5.0 as a minimum required). In order to view the PLC data in the 'PLC Program Viewer' web page of an '140NOE77111', the Unity application signature must be synchronized with the Web Designer application.
To synchronize the Unity application signature with the Web Designer application:
- Export the Unity application to an .'xef' file.
- Open the Web Designer application.
- Open the Devices tab.
- Click on the 'PLC Program' tab.
- Click on 'Program' in the 'Logical view' window to select it.
- Click on Import.
- Select the Unity .xef file.
- Click on Open.
- Browse for the Unity '.stu' file.
- Click on Import.
Note: The synchronization must be performed again if there is a logic change in the Unity application within the PLC.
Legacy KB System (APS) Data: RESL208907 V1.0, Originally authored by AlCh on 05/20/2013, Last Edited by AlCh on 05/20/2013
Related ranges: Modicon Quantum NOE - TR
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.