SMTP server returned error “Illegal address syntax from unknown in MAIL command:” when emailing the historical logs from an EGX300
Issue
The SMTP server returned the following error:

Nov 26 09:16:03 ip-10-10-20-165 postfix/smtpd[23309]: warning: Illegal address syntax from unknown[192.168.0.64] in MAIL command: test@Schneider-electric.com

Also, the diagnostic page of the EGX300 shows a "connection error" under the SMTP portion.

Product Line
EGX300

Environment

EGX300 built in webpage configuration

Cause
The From Address: and To Address: are not in a format that the SMTP server recognizes.
SMTP server returned error “Illegal address syntax from unknown in MAIL command:” when emailing the historical logs from an EGX300




Resolution
Add the signs "<" and ">" to the From Address: and To Address: fields.

SMTP server returned error “Illegal address syntax from unknown in MAIL command:” when emailing the historical logs from an EGX300
Now, verify proper email operation.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie