How to perform a master reset on the COM'X 200 / COM'X 210 / COM'X 510

Issue:
A user may not know how to reset the COM'X 200, COM'X 210 or COM'X 510 to its default factory settings.

Product Line:
COM'X 200, COM'X 210
EBX200, COM'X 510

Environment:
Factory reset on the COM'X 200, COM'X 210 and COM'X 510

Cause:
There may be a need to reset a COM'X to the default factory settings.

Resolution:
NOTICE
HAZARD OF IP ADDRESS CONFLICT
Disconnect the Com'X from any Ethernet networks before resetting the IP settings to factory values.
Failure to follow these instructions can result in impaired communications.


Note: When following the procedure below, all data and logs that have been stored are erased.

To reset the Com'X completely, follow this procedure to set all configuration settings to factory values:
  1. Turn off the Com'X by disconnecting the control power and wait until the power LED is off.
  2. Press simultaneously the Backup button (7) and Wi-Fi button (8) on the Com'X front face and turn on the Com'X. Hold the buttons for at least 10 seconds until the power LED flashes three times.
  3. Release the buttons. The Com'X reboots.
  4. Wait for the Com'X to restart completely. The power LED is:
  • orange when the Com'X is starting.
  • green when the Com'X has been reset to factory settings and is ready to be configured.


Schneider Electric Česká republika

Zjistěte více

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.