Video: How do I customize short message e-mail alarm actions in Data Center Expert?

Issue:
Customizing short message e-mail alarm actions in StruxureWare Data Center Expert

Product Line:
StruxureWare Data Center Expert (DCE)

Environment:
StruxureWare Data Center Expert (DCE)

Cause:
E-mail notifications from DCE come in a pre-defined format that can not be edited.  To customize e-mail notifications, short message e-mail alert actions need to be used.

Resolution:



1) Open the DCE Client and go to: Alarm Configuration menu > Manage Alarm Actions.

2) Click on Create and then select Short Message E-Mail.  Select Next.

3) Provide an Action Name and add in the e-mail addresses that this alarm action will be sent to.

4) The subject and message fields can be customized using a defined list of macros, which are available on

https://community.se.com/t5/Manage-Alarm-Actions/Alarm-macros-for-SMS-email-alarm-action-settings-on-the-DCE/ta-p/461096

NOTE: You can use spaces, text, and return lines to organize the data that will be sent in the e-mail.

5) Associate your new alarm action to a notification policy, for instructions see Data Center Expert | Video: How do I configure StruxureWare to send e-mail notifications?

Schneider Electric Česká republika

Zjistěte více
Řada:
Produkt:
Zjistěte více
Řada:
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie