Issue:
Customer is looking for equivalent to 5% line reactor on the Altivar Process drive.
Product line:
ATV630, ATV600, Altivar Process
Resolution:
The drive's standard internal DC choke plus a 3% line reactor. Adding an external line reactor will yield a 5% line impedance equivalence.
Schneider Electric does not offer Line reactors for the Altivar Process Drives. Please contact a manufacturer, such as MTE Corp, for selection.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Customer is looking for equivalent to 5% line reactor on the Altivar Process drive.
Product line:
ATV630, ATV600, Altivar Process
Resolution:
The drive's standard internal DC choke plus a 3% line reactor. Adding an external line reactor will yield a 5% line impedance equivalence.
Schneider Electric does not offer Line reactors for the Altivar Process Drives. Please contact a manufacturer, such as MTE Corp, for selection.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Publikováno pro:Schneider Electric Česká republika

