Video: How to configure a Vista grouping object to open the correct meter diagram?
Issue
Customer would like configure a Vista grouping object to open the correct meter diagram.

Product Line
ION Enterprise 5.6, 6.x
Struxureware Power Monitoring 7.x
Power Monitoring Expert 8.x

Environment
Vista

Resolution

Procedure video YouTube
  1. Right-click on the grouping object to open the Grouping Object Configuration window
  2. Specify Node
    • Select the Node tab
User Diagram network
  • Select Custom and navigate to the desired meter.
Meter diagram
  1. (Optional) Specify the grouping object image
    • In the Display tab, select Custom
    • Select the desired image. Images of native devices are located in \Power Monitoring Expert\config\diagrams\images\default
Specific group object
  1. Specify the Action
    • In the Action tab, select Open Diagram for Meter Template
Meter diagram template
  1. Press OK
  2. Press Save to save the changes
  3. Double-click on the grouping object to verify the grouping object functions properly