140EHC10500 stops counting after the RIO cable is disconnected.
The 140EHC10500 stops counting when the RIO cable is disconnected.
Product Line
Quantum 140EHC10500 High speed Counter module.
Environment
Windows 10, ProWORX 32, Unity
Issue
If you disconnect the RIO cable from the Remote IO drop that contains an 140EHC10500 High Speed Counter module,
the module stops counting.
This works as designed. If the CPU loses communications with the 140EHC10500, it is designed to stop counting.
when this happens, the outputs will be set the to the selected output behavior.
When the RIO cable is plugged back, the module will need to be restarted. For additional information, reference page 30 and 69 in the attached user manual.
Publikováno pro: Schneider Electric Česká republika


Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.