Jak vám dnes můžeme pomoci?
Checkbox to turn on 87T protection is disabled in SFT2841 for Sepam Series 80
Issue
User is unable to enable 87T protection because the checkbox is disabled or grayed out and cannot be checked.

Product Line
Sepam series 80
Environment
SFT2841 Software
Cause
The relay does not meet the Un1/In and/or Un2/In' constraints:

Notation:
Resolution
Verify the Sepam configuration.
User is unable to enable 87T protection because the checkbox is disabled or grayed out and cannot be checked.
Product Line
Sepam series 80
Environment
SFT2841 Software
Cause
The relay does not meet the Un1/In and/or Un2/In' constraints:
Notation:
S: HV/LV transformer rated power
Un1: Winding 1 rated voltage
Un1: Winding 1 rated voltage
Located in SFT2841 Sepam settings > Particular characteristics: "Un1"
Un2: Winding 2 rated voltage
Located in SFT2841 Sepam settings > Particular characteristics: "Un2"
In: Winding 1 CT rated current
Located in SFT2841 Sepam settings > CT-VT sensors: "Rated current (In)"
I'n: Winding 2 CT rated current
Located in SFT2841 Sepam settings > CT-VT sensors: "Rated current (I'n)"
Resolution
Verify the Sepam configuration.
- Sepam settings > CT-VT sensors: confirm that values are correct for the CT rated current on both Winding 1 (In) and Winding 2 (I'n)
- Sepam settings > Particular characteristics: confirm that values are correct for the rated voltage on both Winding 1 (Un1) and Winding 2 (Un2) sides. Also verify that Rated Apparent Power is correct.
- Once the system configuration has been validated, verify that the equations listed under "Cause" are satisfied. If the equations are not satisfied and all system configuration is correct, 87T protection may not be supported on the specific system.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.